数字量输出型直流电压互感器的误差特性分析Error characteristic analysis of digital output type DC voltage transformer
李登云,雷民,熊前柱,聂琪,沈曙明,章江铭
摘要(Abstract):
针对数字量输出型直流电压互感器实际误差情况及误差特性研究不足的现状,建立数字量输出型直流电压互感器的误差分析模型,完成现场校准试验,得到实际误差情况,并详细分析误差特性。结果表明,数字量输出型直流电压互感器存在超差现象,但可以通过误差修正达到0.2级要求;基本误差的线性度为0.1%~0.2%;升降变差和短时稳定性均在10-4数量级;存在零点漂移现象,经过零点修正,线性度优化了0.08%,10%额定电压下的测量准确度提高了0.1%。
关键词(KeyWords): 数字量输出;直流电压互感器;误差特性;误差分析模型;线性度;零点漂移
基金项目(Foundation): 国网公司科技项目(JL71-15-042)~~
作者(Author): 李登云,雷民,熊前柱,聂琪,沈曙明,章江铭
DOI: 10.16652/j.issn.1004-373x.2018.04.030
参考文献(References):
- [1]项琼,王欢,杜研,等.电力电压互感器在线群校准技术研究[J].电测与仪表,2016,53(3):32-37.XIANG Qiong,WANG Huan,DU Yan,et al.Research on group online error calibration for power voltage transformer[J].Electrical measurement&instrumentation,2016,53(3):32-37.
- [2]章述汉,周一飞,李登云,等.±800 k V换流站直流电压互感器现场校准试验[J].高电压技术,2011,37(9):2119-2125.ZHANG Shuhan,ZHOU Yifei,LI Dengyun,et al.On-site calibration test of±800 k V convertor station DC potential transformer[J].High voltage engineering,2011,37(9):2119-2125.
- [3]李前,李鹤,周一飞,等.±800 k V直流输电系统换流站直流电流互感器现场校准技术[J].高电压技术,2011,37(12):3053-3058.LI Qian,LI He,ZHOU Yifei,et al.On-site calibration technology of DC current measurement device in converter station of±800 k V UHVDC transmission project[J].High voltage engineering,2011,37(12):3053-3058.
- [4]QIN Xiaohui,ZENG Pingliang,ZHOU Qinyong,et al.Study on the development and reliability of HVDC transmission systems in China[C]//Proceedings of IEEE International Conference on Power System Technology.Wollongong:IEEE,2016:1-6.
- [5]易荣,岳伟,张海涛,等.多端柔性直流输电系统中混合运行方式分析[J].电网与清洁能源,2014,30(12):21-26.YI Rong,YUE Wei,ZHANG Haitao,et al.Analysis on mixture operation mode of VSC-MTDC transmission system[J].Power system and clean energy,2014,30(12):21-26.
- [6]查鲲鹏,刘远,王高勇,等.±1 100 k V特高压换流阀直流耐压试验方法研究[J].电工技术学报,2013,28(1):87-93.ZHA Kunpeng,LIU Yuan,WANG Gaoyong,et al.Study of DC test method of 1 100 k V UHVDC valve[J].Transactions of China Electrotechnical Society,2013,28(1):87-93.
- [7]张健康,粟小华,胡勇,等.智能变电站保护用电流互感器配置问题及解决措施[J].电力系统保护与控制,2014,42(7):140-145.ZHANG Jiankang,SU Xiaohua,HU Yong,et al.Problems and solutions of configuration scheme of current transformer used by protection in smart substation[J].Power system protection and control,2014,42(7):140-145.
- [8]柏航,徐雁,肖霞,等.HVDC电子式电流互感器现场校准方法及关键问题[J].中国电机工程学报,2016,36(19):5227-5235.BAI Hang,XU Yan,XIAO Xia,et al.Research on field calibration methods and key problems for HVDC electronic current transformers[J].Proceedings of the CSEE,2016,36(19):5227-5235.
- [9]张杰,胡媛媛,刘飞,等.高压直流互感器现场校验关键技术[J].高电压技术,2016,42(9):3003-3010.ZHANG Jie,HU Yuanyuan,LIU Fei,et al.Critical technology of on-site calibration system for DC electronic instrument transformer[J].High voltage engineering,2016,42(9):3003-3010.
- [10]郭吉伟,梁魁,董凌凯.有源电子式电流互感器高压侧电源的研究[J].现代电子技术,2008,31(18):20-22.GUO Jiwei,LIANG Kui,DONG Lingkai.Research of the high potential circuit power supply for active electronic current transformer[J].Modern electronics technique,2008,31(18):20-22.